Frequently Asked Questions (FAQ)
Q:How to clean the dust on the surface of the windings of a dry-type transformer?
A:After power outage, use dry compressed air (pressure ≤ 0.3 MPa) for blowing; stubborn dust can be gently brushed off with a brush; water or chemical cleaners must not be used; after cleaning, measure the insulation resistance again.
Q:What are the reasons for excessive noise when the transformer is operating? How can the noise be reduced?
A:Reasons: Loosening of core, deformation of windings, resonance of components, failure of cooling system, influence of grid harmonics. Measures: Tighten the core clamps; Correct the position of windings; Adjust the shock absorption devices of cooling fans / oil pumps; Install soundproof covers; Address grid harmonics.
Q:What issues should be noted when connecting the transformer to the distribution cabinet?
A:Use copper busbars or cables for connection, with the conductor cross-section meeting the current-carrying requirements; the connection points need to be treated with tin plating or silver plating to reduce contact resistance; install lightning arresters and disconnect switches on the high-voltage side to facilitate maintenance; add insulating covers for the busbars on the low-voltage side and mark the phase sequence; after connection, check the insulation and phase sequence to ensure there are no errors.
Q:Why are dry-type transformers preferred for power distribution in high-rise buildings?
A:Dry-type transformers are oil-free and do not have the risks of oil leakage or explosion. They have high fire safety. The volume is relatively small, making them easy to install in the distribution rooms of buildings. The maintenance is simple and they meet the fire protection and space requirements of high-rise buildings.